SF4C Safety light curtain
78
Installing the muting sensor with PNP output
0V 0V0V 0V
Muting input 1 Muting input 2
Muting
sensor A
Muting
sensor C
Muting
sensor B
Muting
sensor D
Installing the muting sensor with NPN output
Muting function
Muting sensor A
Muting sensor B
Muting sensor C
Muting sensor D
Reception status
Beam
received
Beam
blocked
Control output
(OSSD 1, OSSD 2)
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
50ms to 1 sec. (Note 1)
7ms or less
30ms to less than 3 sec.
Time diagram of the muting function
NOTE
1. When the diagnosis function for the muting lamp is active: If the muting lamp
does not light up after 1s, the muting function is deactivated.
When diagnosis function for the muting lamp is not active: The muting
function is activated with a delay of 50ms after the input conditions of the
muting sensor A (C) and B (D) are satisfied.
2. We recommend connecting two muting lamps in parallel. Do not exceed 6W.