Page 16     
Drive Start-up 
Before Applying Power: 
•  Read the Safety section at the front of the QuickStart. 
•  Ensure that all local electric codes are met. 
•  Check for damage to equipment. 
•  Check for loose ends, clippings, filings, drilling swarf etc. lodged in the drive and 
system. 
•  Check all external wiring circuits of the system - power, control, motor and earth 
connections. 
•  Ensure that unexpected rotation of the motor in either direction will not result in 
damage, bodily harm or injury. Disconnect the load from the motor shaft, if 
possible. 
•  Check the state of the Motor Thermistor and Brake Resistor connectors. Check 
external run contacts are open. Check external speed setpoints are all at zero.  
•  Ensure that nobody is working on another part of the system which will be 
affected by powering up. 
•  Ensure that other equipment will not be adversely affected by powering up. 
•  Check motor stator connections are correctly wired for Star or Delta as necessary 
for drive output voltage. 
•  Check motor stator connections are correctly wired for Star or Delta as necessary 
for drive output voltage. 
•  Ensure that the SSD_Rail has been correctly installed and securely fastened. 
•  On the 890CS drive, set the line voltage on rotary switch S1. 
•  Check that the STO feature has been disabled. See page 14 of this Quickstart 
Manual. 
•  DANGER: some motors and control methods are not suitable for use with STO. 
Refer to chapter 6 of the Engineering Reference Manual for full details. 
If all connections have been checked, it is time to POWER-UP the drive