5-45 890SD Standalone Drive  
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D 
Powering-up the Unit  
1.  Apply the 3-phase supply to the 890SD Standalone Drive.  
2.  Select LOCAL mode operation:  
♦  The Keypad will display the Remote Setpoint parameter (%). 
3.  You MUST carry out an Autotune if you intend to use the drive in Sensorless Vector Fluxing Mode  
or Closed-Loop Vector Mode - go to page 5-46. If you are using the drive in Volts/Hz Mode (Open-
Loop Drive) an Autotune is not necessary - go to page 5-51. 
 
 
 
 
REMOTE 
LOCAL 
Hold the Stop key down until 
the display spells  
Release the key to display 
the previous menu  
for example,Local Setpoint