B-4  Sequencing Logic 
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D 
Note  1.  JOGGING is set TRUE once the jog cycle has started, and remains TRUE until the  jog cycle has 
finished which is when either the stop delay has finished or another mode is demanded. 
 
2.  STOPPING is set TRUE during the stopping cycles commanded by either RUNNING going low, 
JOGGING going low or if Fast Stop is active, i.e.  SEQUENCING LOGIC is F-STOP ACTIVE.  
 
3.  Once Run and Jog are both FALSE, HEALTHY O/P will be set TRUE. 
Transition of States 
The transition matrix describes what causes the transition from one state to another, for example see 
number 4 below: the transition from “Ready To Switch On” to “Trip Active” is triggered by “TRIP” going 
TRUE. Note – where a state has more than one exit transition, the transition with the lowest number has 
priority. 
Refer to the following table and state diagram. 
1  Power Up 
Switch On 
Disabled 
Power-Up, Restore Configuration or exit from 
Configuration mode. 
2  Switch On Disabled  Trip Active  Trip 
3  Switch On Disabled 
Ready To 
Switch On 
RUN = FALSE,  JOG = FALSE,  NOT FAST STOP  = 
TRUE and NOT COAST STOP = TRUE 
4  Ready To Switch On  Trip Active  Trip 
5  Ready To Switch On 
Switch On 
Disabled 
NOT COAST STOP = FALSE or NOT FAST STOP = 
FALSE 
6  Ready To Switch On  Switched On  RUN = TRUE or JOG = TRUE