EasyManua.ls Logo

Parker ac890 - Page 479

Parker ac890
711 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-83
Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Parameter Descriptions
TOTAL INERTIA
PREF: 27.23
Default: 0.0000 kgm
2
Range: 0.0000 to
300.0000
kgm
2
The total inertia of the motor and load. This is used as part of the speed loop Autotune feature.
STATOR RES
PREF: 27.14
Default: 1.5907 Ω
Range: 0.0000 to 250.0000 Ω
This parameter contains the motor model per-phase stator resistance as determined by Autotune.
LEAKAGE INDUC
PREF: 27.15
Default: 33.76 mH
Range: 0.00 to 300.00 mH
This parameter contains the motor model per-phase leakage inductance as determined by Autotune.
MUTUAL INDUC
PREF: 27.16
Default: 135.02 mH
Range: 0.00 to
3000.00 mH
This parameter contains the motor model per-phase mutual (magnetising) inductance as determined by Autotune.
ROTOR TIME CONST
PREF: 27.17
Default: 136.75 ms
Range: 10.00 to 30000.00 ms
This parameter contains the motor model rotor time constant as determined by Autotune.

Table of Contents

Other manuals for Parker ac890

Related product manuals