D-117
Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
2.05
Determines the time in which the speed setpoint is ramped to zero. This is expressed as the time to ramp from MAX SPEED to
zero.
r sets the initial speed reduction step at the start of the power loss control sequence.
Determines the maximum allowed time of the Power Loss Ride
-Through sequence. Once timeout is reached, the drive is
allowed to Coast to Stop and eventually trip on UNDERVOLTS.
This diagnostic is set to TRUE while the Power Loss Ride
-Through sequence is active.