4-35 890CS & 890CD Common Bus Units   
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D 
 
 
 
 
 
1.  Apply the 24V DC. 
2.  Check that all keypads are active.  
Note  Because the unit is powering up without the 3-phase connection, the keypad will display a trip indicating 
that the supply is missing. The trip displays are shown below. Press the 
 key whenever this message 
appears to clear it from the screen.  
 
6511 Keypad 
6901 Keypad 
890CD : 
TRIPPED
 
UNDERVOLTAGE
 
***
***
890CS : 
TRIPPED
 
SUPPLY LOSS
 
***
***
 
If the unit is not powering-up with 24V DC: check your supply; check your connections at X01 and 
X13; check the keypad is fitted correctly. If you are still experiencing problems, please contact 
Parker SSD Drives. 
Initial Power-Up Conditions 
The unit will initialise in Remote Mode from factory conditions. 
The Keypad will display the Input Current (%) on the 890CS Common 
Bus Supply, and the Remote Setpoint parameter (%) on the 890CD 
Common Bus Drive.