Programming D-224
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
2PREF Name Block Type Range Default ro\rw Notes
92.22 SEQUENCER
STATE
SEQUENCING
LOGIC
ENUM 0 : START DISABLED
1 : START ENABLED
2 : SWITCHED ON
3 : READY
4 : ENABLED
5 : F-STOP ACTIVE
6 : TRIP ACTIVE
7 : TRIPPED
START DISABLED ro Output
92.23 REMOTE REV OUT SEQUENCING
LOGIC
BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
92.24 HEALTHY SEQUENCING
LOGIC
BOOL 0 : FALSE
1 : TRUE
TRUE ro Output
92.25 START DELAY SEQUENCING
LOGIC
REAL 0.000 to 30.000 s 0.000 s rw
92.26 FAN RUNNING SEQUENCING
LOGIC
BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
92.27 CONTACTOR
DELAY
SEQUENCING
LOGIC
REAL 1.0 to 10.0 s 10.0 s rw
93.01 ENABLE AUTO RESTART BOOL 0 : FALSE
1 : TRUE
FALSE rw
93.02 ATTEMPTS AUTO RESTART INT 1 to 10 5 rw
93.03 INITIAL DELAY 1 AUTO RESTART REAL 0.0 to 600.0 s 10.0 s rw
93.04 ATTEMPT DELAY 1 AUTO RESTART REAL 0.0 to 600.0 s 10.0 s rw
93.05 TRIGGER 1 WORD
1
AUTO RESTART WORD 0000 to FFFF 0000 rw
93.06 TRIGGER 1 WORD
2
AUTO RESTART WORD 0000 to FFFF 0000 rw
93.07 INITIAL DELAY 2 AUTO RESTART REAL 0.0 to 600.0 s 0.1 s rw
93.08 ATTEMPT DELAY 2 AUTO RESTART REAL 0.0 to 600.0 s 0.1 s rw