Technical Specifications E-12
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Electrical Ratings: 890CS Frame B, 500V
Output current must not be exceeded under steady state operating conditions.
FRAME B : 32A AC rms Input Current (nominal power 15kW)
Model Number
890CS-532320B (890CS/5/0032B)
Operating Voltage
208V to 500V ±10%
Nominal Operating Voltage
V
208/230
380/415
460
500
Input Current
A
32
Continuous RMS Output Current
A
40
Output Power
7.5kW/10HP
15kW
25HP
18kW
Power Loss
W
105
105
105
105
Output Overload
150% overload for 60 seconds
Dynamic Brake Current Rating (See Note 1)
A
20
20
20
20
Input Bridge I
2
t
A
2
s
1000
Prospective Short Circuit Current
kA
65
FRAME B : 54A AC rms Input Current (nominal power 30kW)
Model Number
890CS-532540B (890CS/5/0054B)
Operating Voltage
208V to 500V ±10%
Nominal Operating Voltage
V
208/230
380/415
460
500
Input Current
A
54
Continuous RMS Output Current
A
65
Output Power
15kW/20HP
30kW
45HP
37kW
Power Loss
W
195
195
195
195
Output Overload
150% overload for 60 seconds
Dynamic Brake Current Rating (See Note 1)
A
40
40
40
40
Input Bridge I
2
t
A
2
s
1500
Prospective Short Circuit Current
kA
65
Note 1: Based on 33% duty cycle at a braking resistor appropriate for braking at 100% of drive rated power.