E-47 Technical Specifications
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Wire Sizes
Model Number
Description
Power Input (Bus Bar)
Power Output (Wire)
890SD-532590D
Wire size AWG / mm
2
4 / 25.0
4 / 25.0
890CS Branch Protection Fuses (North America)
It is recommended that UL Listed (JDDZ) non-renewable cartridge fuses, Class K5 or H;
or UL Listed (JDRX) renewable cartridge fuse, Class H, are installed upstream of the drive.
Model Number
Input Fuse Rating (A)
Model Number
Input Fuse Rating (A)
Constant
Quadratic
Constant
Quadratic
208VAC TO 500VAC ±10%
Frame B
Frame D
890CS-532320B
40
-
890CS-533108D
125
-
890CS-532540B
60
-
890CS-533162D
175
-