5-5 890SD Standalone Drive
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
11
B
D
890 Operating Conditions
Humidity
Maximum 85% relative humidity at 40°C (104°F) non-condensing
Altitude If greater than 1000m above sea level, derate by 1% per 100m to a
maximum of 2000m
Atmosphere Non flammable, non corrosive and dust free
Climatic Conditions Class 3k3, as defined by EN50178.
Vibration The product has been tested to the following specification:
Test Fc of EN60068-2-6
10Hz<=f<=57Hz sinusoidal 0.075mm amplitude
57Hz<=f<=150Hz sinusoidal 1g
10 sweep cycles per axis on each of three mutually perpendicular axis
Safety
Pollution Degree
Pollution Degree ll (non-conductive pollution, except for temporary
condensation)
Europe When fitted inside an enclosure, this product conforms with the Low
Voltage Directive 2006/95/EC using EN50178 to show compliance.
North America/ Canada Complies with the requirements of UL508C as an open-type drive.
Conformal Coated
Product
Conformal coating increases the product’s resistance to certain
climatic conditions.
Note conformal coating, where effective, will only mitigate the effects
being considered.