I/O interface description
 
GVI Product Manual: Frames C, D & E
 
34  192-300300N1 GVI Frames C, D & E 2019-9 
8.8  Open Drain Output 
8.8.1.  Function 
Open Drain outputs can be used for operating services such as the main contactor, relay, hydraulic valves, 
parking brake, etc.  
The Open Drain outputs may work in different modes depending on the expected behavior of the connected 
load. The operating modes are: 
•  On/Off 
•  Voltage control (Pull/Hold) 
•  Current control 
•  Open-loop PWM control 
In order to utilize the built-in free-wheeling diodes, open drain 4, 5 and 6 loads must be supplied from the 
HIGH_SIDE_IN, while the open drain 1, 2 and 3 loads can be supplied from either HIGH_SIDE_IN or 
HIGH_SIDE_OUT. Recommended wiring of loads, utilizing redundant shut-off capability of the high side 
switch, is shown in Figure 22. 
In case the vehicle design does not allow usage of the built-in free-wheeling diodes, i.e. if the return path 
integrity cannot be guaranteed in all situations, external free-wheeling diodes must be applied over the 
inductive loads controlled by the open drain outputs. 
Closed loop 
current control 
Table 8. Open drain functionality 
PWM frequencies are settable. The setting will apply to all PWM outputs. PWM shall only be used for 
inductive loads such as relays, contactors, motor brakes or hydraulic valves. 
Each “open loop PWM” output can be voltage controlled with separate pull and hold voltage software 
parameters. 
The current measurement can be used as open-load and overload detection. Each output has individual 
hardware for short circuit detection and rapid shut off to prevent damage to the circuit. 
Refer to chapter 13.4.5 for current measurement range. The current is only measured when the Open drain 
MOSFET is ON, see circuit in Figure 21. Current measurement offset error is compensated in software. 
When using current control it is possible to add dithering by giving the current a low frequency, low amplitude 
oscillating waveform. 
Dithering is typically used when controlling proportional valves to create microscopic movements in the valve 
to prevent it from “sticking”. Successful dithering improves the valve response for small changes. 
Table 9. Dithering frequency in fixed steps 
The dithering frequency and current amplitude are adjustable. Actual dithering amplitude is dependent on 
load inductance, dithering frequency and current control regulator parameters i.e. P-gain and I-gain.