TROUBLESHOOTING
70 IPA Hardware Installation Guide
E8 Continuous Current = 0
This parameter is set to zero (0). To correct the error, you must set a
non-zero value. Refer to your motor specifications for the correct value.
(C1 Continuous Current)
This parameter is set to zero (0). To correct the error, you must set a
non-zero value. Refer to your motor specifications for the correct value.
(C3 Peak Current)
E10 Used Drive Continuous Current
Warning
The continuous current of the motor is higher than the continuous
current rating of the drive/controller. Use the continuous current rating
for the drive/controller.
E11 Torque Rating > Peak Power
Rating Warning
The motor’s torque rating is too high for the power level of the
drive/controller. Use the drive/controller’s torque rating.
E12 Used Drive Peak Current
Warning
The peak current of the motor is higher than the peak current rating of
the drive/controller. Use the drive/controller’s value for peak current.
This parameter is set to zero (0). The drive/controller will not enable
Velocity or Position Modes. To correct the error, you must set to a non-
zero value. Refer to your motor specifications for the correct value. (C11
Motor Rotor Inertia / Forcer Mass)
This parameter is set to zero (0). The drive/controller will not enable
Velocity or Position Modes. To correct the error, you must set to a non-
zero value. Refer to your motor specifications for the correct value. (C10
Motor Damping)
The drive/controller is faulted.
E27 Bridge Hardware Fault
Excessive current or short on the H-bridge.
E28 Bridge Temperature Fault
Excessive current being commanded:
1. If the application is operating in the peak range, limiting the peak
current setting with DMTLIM can limit the current commanded
and lower the bridge temperature. Default DMTLIM is 3 x
continuous current, perhaps lowering it to 2.5 x continuous
current or 2 x continuous current can help. This, however, will
limit the motor’s available torque, which may increase position
error and possibly cause a position error fault.
2. Issue a DIFOLD 1 command. This command enables the “current
foldback” feature in the drive. However, a drive in “foldback”
mode can available torque, which may increase position error
and possibly cause a position error fault.
3. Use a larger IPA amplifier, which would be capable of higher
current outputs.
The bus voltage is too high (>410 VDC). Lower AC Mains voltage
(Motor Input Power) and check for excessive regeneration power. (S22
Transfer Bus Voltage)
The bus voltage is too low (<85 VDC) or there is overly aggressive
acceleration or deceleration. Raise AC Mains voltage (Motor Input
Power). (S22 Transfer Bus Voltage)
Drive/controller current was limited to prevent overheating (warning
only).