5 Commissioning [specialist]
2022/07 99E13331xx-mub-en - V08 17
5.5 Automatic Daylight saving time / Standard time
Activate/deactivate the automatic daylight saving time / standard time
When the controller is delivered, this item is activated.
5.6 Cascade*
At this menu item, the operating parameters (switchover point, duration of backup mode) of the
domestic hot water modules within a cascade are set.
5.7 Scan Modbus*
SCAN MODBUS
STATUS
Server 1
OK
Server 2
---
Server 3
---
MB3.10
---
The identification of the domestic hot water modules
which are operated in the cascade mode is made via the
menu item
Scan Modbus.
The dot marks which controller type is searched at the
moment.
*This submenu appears if the client (ID1) was selected at "Controller type".
5.8 Nominal temperature
NOMINAL TEMPERATURE
60 °C
MIN : 35
MAX : 75
Setting the desired nominal temperature of the hot water.
5.9 Functions
Activate/deactivate the functions and further, corresponding settings.
When the domestic hot water module is delivered, as well as after a reset to factory settings, all
functions are deactivated apart from
Over temperature switch off
.
You will find detailed information on this in chapter 17.
5.10 Finish with protocol
Save the commissioning with creating a protocol. For this, an external memory (USB flash drive)
must be connected to the service interface / USB port. This interface can only be accessed after
removal of the front panel, see chapter 4.1.