17 Description of function
2022/07 99E13331xx-mub-en - V08 35
Operation mode "temperature control"
As a temperature sensor for the temperature control, either the cold water sensor (T-CW) or an
external temperature sensor can be selected. If the temperature measured at the selected
sensor falls below the switch-on temperature, the circulation pump is actuated. If the
temperature measured at the selected sensor is higher than the switch-off threshold (switch-on
temperature + ΔT Off), the circulation pump is switched off.
Operation mode "time control"
There are two possibilities to set the circulation pump in the menu item Time control:
Continuous operation - the circulation pump runs permanently without interruption
Time control settings - the circulation pump runs only in a user-defined time window.
If the current time lies within a defined time window, the circulation pump is actuated. For each
day of the week, up to 5 time windows can be defined.
At
Circulation → Time control → Time control settings
, choose the
Timer
(Set) and define one or
multiple time windows on the desired days.
First set the hour, then the minutes of the time when the circulation is meant to start.
After confirmation, set the hour and the minutes of the time when the circulation is meant to
stop. Please also confirm the end time to completely define the time window.
The time setting of a day can be copied to another day. To copy the settings, select the menu
item
Copy
. Then, select the day or the days to which the setting is meant to be copied.
Finally, select the menu item
Confirm
in the last line to complete the copying.
At
Circulation → Time control → Time control settings → Preview
, an overview of the defined
circulation times is displayed.
Operation mode "demand"
Is a tap open for a few seconds (max 5 s) and closed, the flow rate sensor detects this tap
impulse. If the
Demand
mode is activated, this tap impulse initiates the switch-on of the
circulation pump for the determined runtime.
After the end of the runtime, the circulation pump is locked for a defined break duration.
During the runtime as well as during the break, no new demand is accepted.
Setting changes made during a circulation in process will not be applied until after the
circulation process has ended (break duration included).