EasyManua.ls Logo

PAW FC3.10 - Page 37

PAW FC3.10
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17 Description of function
2022/07 99E13331xx-mub-en - V08 37
Parameters
Meaning
Adjustment range
Factory setting
Circulation active Activate the function On, Off Off
Temperature control Submenu for
settings of the
temperature control
On, Off Off
Switch-on temperature Setting the switch-
on temperature
35 ... 75 °C 55 °C
ΔT Off ΔT for the
determination of the
switch-off
temperature
2 ... 10 K 2 K
Time control Submenu for
settings of the time
control
On, Off Off
Continuous operation Continuous
operation
On, Off Off
Week settings Timer function On, Off On
Timer Setting of the time
windows
Monday ... Friday
00:00 ... 23:59
-
Demand Submenu for
settings of the
demand
On, Off Off
Work time Work time 00:00 ... 10:00 min 01:00 min
Pause Pause 0 ... 60 min 10 min
Circulation sensor Selection of the
sensor
T-CW, external
sensor (S2 (only for
FriwaMini), S3)
T-CW
Pump speed Setting of the pump
speed
0 ... 100 % 100 %

Table of Contents

Other manuals for PAW FC3.10