MODE6 CONFIG
IN2:RUN
Set the second input (IN2):
– STOP (input enabled to stop the second pump)
– RUN (input enabled to start the second pump)
– 2RUN (input enabled to start the second pump alone)
– OFF (input disabled)
MODE6 CONFIG
LOGIC:ALTERN.
If the system has two electric pumps, enable (ALTERN.) or disable (SIN-
GLE) the alternating logic.
MODE6 CONFIG
DRY RUN EN:OFF
Enable (ON) or disable (OFF) dry running protection
MODE6 CONFIG
DRY LOGIC:COS
Set whether the dry running stop logic is based on the motor current read-
ing (CURR) or cosφ reading (COS)
MODE6 CONFIG
COSFI REC:ON
Enable (ON) or disable (OFF) automatic COSFI recovery when it is below
COSFI MIN (dry running)
With COSFI RECOVERY, the control panel attempts to automatically recover
an electric pump that is in the dry running alarm state (COSFI read < COSFI
minimum)
MODE6 CONFIG
REC TIME:2m
Recovery time for automatic deactivation of the dry running alarm.
The control panel attempts automatic recovery after the set time, and then
doubles it on each subsequent cycle (e.g. 2 min, 4 min, 8 min ...), up to the
maximum recovery time (see the next parameter).
Default 2 min Range 0-10 min Step 1 min
MODE6 CONFIG
MAX REC T:60m
Maximum recovery time for automatic deactivation of the dry running
alarm.
The control panel attempts automatic recovery up to the set maximum val-
ue (e.g. every 60 min).
Default 60 min Range 0-120 min Step 1 min
MODE6 CONFIG
P1:3.0 bar
Set the rst activation threshold to a specic pressure.
This parameter denes the rst pressure threshold (P1), above which both
electric pumps are deactivated.
If the pressure is below this set value (P1) minus the dierential value
(DP1), a single pump is activated according to the alternating logic.
Default 3 bar Range 0–40 bar Step 0.1
MODE6 CONFIG
DP1:0.5 bar
Set the dierential value (DP1) to a specic pressure.
This parameter denes the dierence between the activation and deactiva-
tion levels with respect to the rst activation threshold (P1)
Default 0.5 bar Range 0-P1 Step 0.1