How to fix communication error on the fieldbus in Pepperl+Fuchs LB?
- CCheryl HullSep 12, 2025
To resolve a communication error on the fieldbus with Pepperl+Fuchs I/O Systems, ensure the cables are securely connected. Verify the transmitting and receiving lines are correctly wired and not swapped. Confirm that the nodes are arranged in a linear fashion without any branches, as a star-shaped layout is not permitted. Activate the terminator, ensuring there are exactly two terminators per segment, one at the start and one at the end. In the configuration software, check that the selected address matches the remote I/O station address. Also, verify whether the master read cycle and the com unit watchdog are coordinated within the configuration software.