EasyManua.ls Logo

Perkins 1204F-E44TA - Def Component Relative Positions; DEF Tank to PEU

Perkins 1204F-E44TA
41 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1204F - DEF System Supplement
There must be a minimum of 150mm clearance above the filter cap to provide sufficient
space to service the filter.
o Access for a 22mm hex socket is required to replace the filter cap (to 14Nm +/-
2Nm)
Minimum clearance of 125mm must be given for DCU connector removal
Minimum clearance of 65mm must be given for DEF inlet and outlet connector fit/removal
Minimum clearance of 25mm should be given to the left and right side of the PEU
The pump must be specified to the correct voltage of the machine and wired in accordance
with the Electronic A&I manual
There is an M8x1.5 tapping (21mm depth) on the RHS top face of the DCU which should
be used for strain relief of the electrical harness. Torque limit is 15Nm=/-1.5Nm.
The PEU must not be painted
2.8 DEF component relative positions
All DEF system configurations require validation and approval to ensure the system
requirements are met.
2.8.1 DEF tank to PEU
There are limitations on the relative position of the tank base level to the PEU inlet
connection; these are detailed in fig 2.3 below.
Fig 2.3 – DEF Tank Relative Position to PEU
The longest DEF suction line allowed is 2000 mm
The lowest point on the DEF suction line, which attaches to the PEU, should be no more
than 190 mm ± 2 mm lower than the bottom of the standard tank.
The highest point on the DEF suction line, which attaches to the PEU, should be no more
than 805 mm ± 2 mm higher than the bottom of the standard tank.
A&I manual Publication TPD 1832 Production issue 3. Page 11 of 41

Table of Contents

Other manuals for Perkins 1204F-E44TA

Related product manuals