DIESEL ENGINE DATA
4006/8 Diesel, May 1998 11
PROTECTION EQUIPMENT
Before resetting protection equipment, it must be established whether special settings (for
that individual engine) have been specified in the engine sales contract. This is particularly
important with ALL high water temperature settings.
Standard settings for protection equipment are as follows:
Caution: The above standard settings do not supersede any settings specified in the engine
sales contract.
AIR STARTING
INSTRUMENT PANEL (ENGINE MOUNTED)
COOLANT JACKET HEATING
4006 4008
Shutdown switches
Alarm Shutdown
High Oil temperature 105°C 110°C
Low oil pressure 2.06 bar (30 lb/in²) 1.93 bar (28 lb/in²)
Hight water temperature
71°C Thermostat 91°C 96°C
Overspeed
15% (on 1500 rev/min)
7% (on 1800 rev/min)
Air starter pressure 30 bar
Compressed air supply 17 bar
Type Ingersoll-Rand Type SS350
Type GALI A25
Normal Operation
Oil pressure Between 300-560 kPa (42.6-80 lb/in²)
Oil temperature Between 80-90°C (176-194°F)
Water temperature Between 65-85°C (149-185°F)
Exhaust temperature See Product Information Manual
Boost pressure See Test Certificate
Heater 1 x 2 kW 1 x 4 kW