EasyManua.ls Logo

Phase Technologies SD Series - Page 47

Phase Technologies SD Series
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
41 | P a g e
Table 15 - Constant Pressure Parameters
DISPLAY MESSAGE
DESCRIPTION
DEFAULT/MIN
/MAX VALUE
BROKEN PIPE PSI
psi at which unit will determine there is a broken pipe. Value of zero
disables this feature.
0/0/150
BROKEN PIPE TIME
In minutes. Time at which measured pressure is below BROKEN PIPE
PSI, unit will fault out.
0/0/9999
T OFF
In seconds. Used to prevent short cycling in CP systems. If the motor
was off during the last cycle for a period greater than TOFF, the
minimum on time of the motor is T1ON. If the motor was off for a period
less than TOFF, the minimum on time of the motor is T2ON. Default
values give a minimum cycle time of about 1 minute.
30/0/1000
T1 ON
In seconds. See T OFF above. T1ON should be set to be less than
T2ON.
15/0/1000
T2 ON
In seconds. See T OFF above. T1ON should be set to be less than
T2ON.
60/0/1000
SHUTOFF
FREQUENCY
As Hz. This parameter value is added to the frequency set by the
parameter MINIMUM FREQ. The combined value is the frequency at
which drive will enter sleep mode when pressure is controlled at the set
point.
12/0/300
BOOST AMOUNT
As psi. The parameter value specifies a pressure increase in psi before
sleep mode. The value is added to psi SETPOINT.
0/0/100
PRECHARGE
FREQUENCY
In Hz. Sets the maximum frequency applied to the motor during the pre-
charge interval.
30/1/120
PRECHARGE TIME
In minutes. Sets the maximum time for pre-charge regardless of any
sensor inputs. A setting of zero disables the pre-charge mode.
0/0/30000
PRECHARGE psi
Used only for analog CP systems. Pre-charge will be terminated when
pressure reaches this set point. Should be set less than psi
SETPOINT.
20/0/200
PROPORTIONAL
GAIN
Multiplier for the analog error signal in an analog constant pressure
system. When parameter is set to a value of zero the keypad displays
SIMPLE MODE and the controller switches to an algorithm which does
not require a gain setting. See Section 7.8, Troubleshooting Constant
Pressure Systems, for details. When using PI control, best results will
be obtained by starting with a value of 5 for PROPORTIONAL GAIN.
5/simple
mode/60
INTEGRAL GAIN
Multiplier for the integral term in PI control of analog constant pressure.
Used to fine tune control of unstable systems. Parameter is disabled
when PROPORTIONAL GAIN is set to SIMPLE MODE. See Section
7.8, Troubleshooting Constant Pressure Systems, for details.
12/0/100
DERIVATIVE GAIN
Used to reduce overshoot and oscillation. Should be used only when
necessary because it tends to amplify noise in the transducer signal. It
may cause the system to become unstable.
0/0/50
PID FILTER GAIN
Controls the rate of frequency increase in response to the error term.
0/0/100
PID FILTER TIME
Sample interval for the PID Filter Gain.
1/0/10

Related product manuals