www.phocos.com 28 | P a g e
08
Solar power feed-in into grid
A PIN code is required to
change this setting. Grid feed-
in / injection may not be legal
at the site of installation.
Contact your dealer formore
details.
Only activate when using the
public grid as AC source, else
your AC ge ne rator and the
Any-Grid could b e damaged.
Disabled (Default) Enabled
09
AC output frequency
Only relevant for Off-Grid
mode
50 Hz (Default, 230Vac models) 60 Hz (Default, 120Vac models)
10
AC output voltage
Only relevant for Off-Grid
mode
Note:To avoid damag e, this
value can only be changed if
the inverter is in Stand-By
mode (AC output turned off).
See chapter “Installing
Multiple Units in Parallel,
Split Phase or 3-Phase
Configuration”for detailed
instructions.
230 Vac (Default, 230 Vac
models)
From 220 ~ 240 Vac in 10 Vac
increments for 230Vac models.
110, 120 and 1 27 Vac for 120Vac
models, default120Vac.
11
Maximum AC source charging
cur rent (b attery side)
If se ttings menu 02 is smaller
than this value, charging will
be limited by the value in
settings me nu 02.
30 Adc (Default) Available values: 2 Adc and 10 ~ 80
Adc (up to 120 Adc for PSW-H-
6.5KW-120 /48V and PSW-H-8KW-
230/48V) in 1 0 Adc increments.
12
Voltage set-pointto switch
from Off-Grid mode to Grid
mode when“SBU priority”is
selected in settings menu 01.
This may be a pe rcentage for
some battery types selected
in sett in
menu 05.
48 Vdc (48 Vdc model Default)
24 Vdc (24 Vdc model Default)
Available values: 44 ~ 57 Vdc in 1
Vdc increments for 48Vdc model.
Available values: 22 ~ 28.5Vdc in
0.5 Vdc increments for 24 Vdc
model.
13
Voltage set-point to s witch
from Grid mode to Off-Grid
mode when selecting “SBU
priority” in settings menu 01.
Battery fully charg ed 54 Vdc (4 8 Vdc model Default)
27 Vdc (2 4 Vdc model Default)
Available values: “FULL”and 48 ~ 64 Vdc in 1 Vdc increments for 48Vdc
model.
Available values: “FULL”and 24 ~ 32 Vdc in 1 Vdc increments for 24Vdc
model.
The battery is considered fully charge d when the float charging phase
is reached.