Function description
Operating Manual PSEN sc B 5 Series
1004508-EN-02
14
4.2 Use of zone sets and monitoring cases
A safety zone and a warning zone constitute a zone set.
A monitoring case is a defined signal at the control inputs for the current machine state. For
one specific machine state, one specific monitoring case can be assigned.
The safety laser scanner uses the defined signal at the control inputs to activate the zone
set, which is assigned to this monitoring case and therefore to a specific machine state.
When a machine has e.g. different operating statuses, a safety laser scanner can be used
to monitor several operating statuses.
When using two zone sets, the monitoring of zone set 1 can be switched to the monitoring
of zone set 2. The switching is controlled by the configurable inputs.
The standard behaviour when switching the monitoring cases does not plan an overlap of
the zone sets.
4.3 Automatic and monitored start/restart
Automatic start/restart
After switching on the safety laser scanner or re-release of the protected field, the safety
laser scanner automatically starts to the ON condition under these conditions:
} both OSSDs are wired correctly and
} no error has occurred and
} the safety zone is free.
If the safety zone is violated, the OSSDs switch to the OFF state.
Monitored start/restart function
The OSSDs switch to the ON state during operation under the following conditions:
} both OSSDs are wired correctly and
} no error has occurred and
} the protected field is clear and
} at least 80 ms have elapsed since switching to the OFF state and
} The start button has been operated and then released again for a min. 0.5 s and a max.
5 s. The start occurs with a falling edge.