44 - ATR142 - User manual
38
a .2.s . p.
Alarm 2 Setpoint Protection
Alarm 2 set protection.
Does not allow operator to change setpoint value.
free
> Default
Lo ck.
Locked
Hi d e
Locked and hidden
39
co o . f.
Cooling Fluid
select type of cooling fluid for Heating/Cooling PID (parameter
7.12)
ai r
Air > Default
oi L
Oil
H2o
Water
40
p.b.m.
Proportional Band Multiplier
1.00-5.00 > Default: 1.00. (parameter 7.12)
41
ov.d.b.
Overlap/Dead Band
overlapping/Dead band (parameter 7.12)
-20.0-50.0% > Default: 0.
42
co.t.c.
Cooling Cycle Time
cycle time for cooling output.
1-300 sec. > Default: 10.
43
c. fLt.
Conversion Filter
ADC filter, number of means on analogue-digital
conversions.
di s .
Disabled
2.s. m .
2 Samples Mean
3.s . m .
3 Samples Mean
4.s. m .
4 Samples Mean
5.s . m .
5 Samples Mean
6.s . m .
6 Samples Mean
7.s. m .
7 Samples Mean
8.s . m .
8 Samples Mean