User manual - ATR142-  27  
t.2.e.a.
Timer 2 End Alarm
Alarm active at elapsing of Timer2 
until any key is pressed.  Option not 
available for Dual sequential Timer and 
Dual Timer Loop.
t.2.w.e.
Timer 2 Warning 
Expiring
Alarm active for the last 5” of Timer2 
t .1 . 2 . s . 
Timer 1-2 Start 
Alarm
Alarm active as long as  Timers 1 and 2 
are in Start mode (Timers active)
t .1 . 2 . e . 
Timer 1-2 End Alarm
Alarm active at elapsing of Timers 1 
and 2 until any key is pressed.  Option 
not available for Dual sequential Timer 
and Dual Timer Loop.
t .1 . 2 . w . 
Timer 1-2 Warning 
expiring
Alarm active for the last 5” of Timers 
1 and 2.
10  Serial Communication
10.1  Slave
ATR142-ABC-T is equipped with RS485, it can receive and 
broadcast data via serial communication using MODBUS RTU 
protocol. The device operates as slave if parameter 59 
mast.
 is 
set as 
di s
. This function enables the control of multiple devices 
connected to a supervisory system (SCADA).
Each controller will answer to a master query only if the query 
contains same address as on parameter 
sL. a d .
 The permitted 
addresses range from 1 to 254 and there should not be 
controllers with the same address on the same line.
Address 255 can be used by the master to communicate with all 
the  connected equipment (broadcast mode), while with 0 all 
the devices receive the command, but no answer is expected.
ATR142 can introduce an answer delay (in milliseconds) to 
master request. This delay has to be set on parameter 58 
se. d e.
.