User manual - ATR171 39
70
op.mo.
Operating mode
Selects operating mode. In model ATR171-23ABC-T, this parameter is visible only
if dip-switches are configured for serial communication (AI2 desabled).
co n t.
Controller (Default)
p r. cy .
Programmed Cycle
2t.s.
2 Setpoints Switch
2t. s .i .
2 Setpoints Switch Impulsive
3 t. s .i .
3 Setpoints Switch Impulsive
4 t. s .i .
4 Setpoints Switch Impulsive
71
au.ma.
Automatic / Manual
Enables automatic / manual selection
di s .
Disabled (Default)
en.
Enabled
en.st.
Enabled with memory
72
d Gt.i .
Digital Input
(par. 70 selection must be
co n t.
or
p r. cy .
). In model ATR171-23ABC-T, this
parameter is visible only if dip-switches are configured for serial communication
(AI2 desabled).
di s .
Disabled (Default: 0)
st.st.
Start / Stop
rn.n.o.
Run N.O. (enables regulation with N.O. contact)
rn.n.c.
Run N.C. (enables regulation with N.C. contact)
L.c.n.o.
Lock conversion N.O. (stop conversion and display value with N.O.)
L.c.n.c.
Lock conversion N.C. (stop conversion and display value with N.C.)
tu n e
Manual Tune (by digital input)
a.ma.i.
Automatic / Manual Impulse
a.ma.c.
Automatic / Manual Contact
t m r.i .
Impulse Start timer
73
ri . G r .
Rising Gradient
Rising gradient for Soft-Start or pre-programmed cycle. In model ATR171-
23ABC-T, this parameter is visible only if dip-switches are configured for serial
communication (AI2 desabled).
0 Disabled.
1..9999 Digit/hour
12
(degrees/hour with decimal visualization if temperature),
Default: 0.