Pixsys ATR144 - GROUP C - rEG.1 - Autotuning and PID 1

Pixsys ATR144
93 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User manual - ATR144- 53
12.c
GROUP C -
r e G .1
- Autotuning and PID 1
36
t u n .1
Tune 1
Selects autotuning type for command 1.
diS a b.
Disabled. If proportional band and integral
time parameters are to set to zero, the
regulation is ON/OFF type.. (Default)
Auto
Automatic (Automatic P.I.D.
parameters calculation )
M a nu.
Manual (launch by keyboards
or by digital input)
OncE
Once (P.I.D. parameters calculation
only at first start)
SY ncH.
Synchronized (Autotuning managed by serial)
37
s.d.t.1
Setpoint Deviation Tune 1
Selects deviation from command setpoint 1 as threshold
used by autotuning to calculate P.I.D. parameters.
0-10000 [digit
1 p. 86
] (degrees.tenths for temp. sensors).
Default: 30.0.
38
p. b . 1
Proportional Band 1
Proportional band or process 1 P.I.D. regulation (Process
inertia).
0 ON / OFF if t.i. equal to 0 (Default)
1..10000 [digit
1 p. 86
] (degrees.tenths for temp. sensors).
39
i . t. 1
Integral Time 1
Integral time for process P.I.D. regulation (process
intertia duration).
0.0...2000.0 sec. (0.0 = integral disabled), Default 0.0
40
d . t. 1
Derivative Time 1
Derivative time for process P.I.D. regulation (Normally ¼
of integral time).
0.0...1000.0 sec. (0.0 = derivative disabled), Default 0