52 - ATR144 - User manual
26
c.de.1
Command Delay 1
Command 1 delay (only in ON / OFF functioning).
-60:00..60:00 mm:ss. Default: 00:00.
Negative: delay when turning off output.
Positive: delay when turning on output.
27
c . S . p .1
Command Setpoint Protection 1
Controls access to the command setpoint 1 value
FrEE
Modification allowed (Default)
Lock
Protected
Hid E
Protected and not displayed
28
v A . t .1
Valve Time 1
Valve time related to command 1 (declared by the
manufacturer of the valve)
1...300 seconds. Default: 60.
29
a.ma.1
Automatic / Manual 1
Enables the automatic/manual selection for command
1
diS a b.
Disabled (Default)
En a b.
Enabled
En.St o.
Enabled with memory
30
i ni .S.
Initial State
Choose the state of the controller when turning it
on. This only works on the version ATR144-ABC-T or
by enabling the Start/Stop from digital input or SET
button.
start
Start (Default)
stop
Stop
s t o r e.
Stored. State of Start/Stop
prior to switching off.
31÷35 Reserved Parameters - Group B
Reserved parameters - Gruppo B