68 - ATR144 - User manual
12.h
GROUP H -
sft.s
- Soft-start and mini
cycle
108
de.st.
Delayed Start
To set the initial waiting time for the delayed start of the
setting or cycle, even in case of a blackout. The elapsed
time is saved every 10 minutes.
0 Initial waiting time disabled: the
controller starts immediately (Default)
00:01-24:00 hh.mm Initial
waiting time enabled.
109
Pr. cY .
Pre-programmed Cycle
Enables special functionings.
diS a b.
Disabled (Default)
En a b.
Enabled (all remote sepoint
functions are inhibited)
110
SS.TY.
Soft-Start Type
Enables and selects the soft-start type
diS a b.
Disabled (Default)
Grad.
Gradient
P erc.
Percentage (with only pre-
programmed cycle disabled)
111
SS. G r.
Soft-Start Gradient
Rising/falling gradient for soft-start and pre-program-
med cycle.
0..20000 Digit/hour (degrees.tenths/hour if
temperature). (Default: 100.0)
112
SS.P e.
Soft-Start Percentage
Output percentage during soft-start function.
0..100%. (Default: 50%)
113
SS. tH.
Soft-Start Threshold
Threshold under which the soft-start percentage
function is activated, at starting.