User manual - ATR227 - 15
  F.PH.A.  Fixed Phase angle control
If this mode is active, the regulation is done as per “time control” (
tiME
), but during the 
activation it is managed a xed choking selected on parameter 45 
F.P.A.P...
8  Conguration
For conguration parameters see par. 10.
Press Display Do
1
 
SET
for 3 sec. 
Display 1 shows 
0000
 with 
the 1st digit ashing, while 
display 2 shows  
PASS
.
2
 or 
Modify the ashing digit 
and move to the next one 
pressing 
SET
.
Enter password 
1234
.
3
SET
to conrm
Display 1 shows the rst 
parameter while display 2 
shows the value.
4
 or 
Slide up/down through 
parameters.
5
SET
 or 
Increase or decrease the 
visualized value pressing  
SET
 and an arrow key.
Enter the new data which 
will be saved on releasing 
the keys. To change another 
parameter return to point 4.
6
 + 
togheter
End of conguration para-
meter change.
The controller exits from 
programming.
8.1  Loading default values
This procedure allows to restore factory settings of the device.
Press Display Do
1
SET
for 3 sec
Display 1 shows 
0000
 with 
the 1st digit ashing, while 
display 2 shows 
PASS.
2
 or 
Modify the ashing digit 
and move to the next one 
pressing 
SET
.
Enter password 
9999
.
3
SET
to conrm 
The device loads default 
settings
Turn o and restart the 
device.