User manual - DRR245 13
6.1.d Serial input
21
19
20
RS485
Shield/Schermo
RS485 Modbus RTU communication.
For networks with more than five instruments supply
in low voltage, preferably Vdc.
Shield must not be grounded (connect to pin 19)
6.1.e Relay Q1 - Q2 output
Q1
5A
230V
1
2
3
6
4
5
Q2
5A
230V
Capacity:
5 A / 250 V~ for resistive loads, 10
5
operations.
20/2 A, 250 Vac, cosφ = 0.3, 10
5
operations.
50
20
10
5
0
1
2 3 4
Contact load current (A)
5
Service life (x10
4
operations)
100
AC125 V
AC125V COS ø=0.4
DC30 V t=7ms
Life Curve
AC250V COS ø=0.4
DC30 V t=15ms
200
AC250V
DC30 V
6.1.f SSR output
11
10
SSR
SSR command 10,5V/30mA.
Short-circuit pins 9 and 10 as in the figure to use SSR
output