14 Table of Anomaly Signals
If installation malfunctions, controller will switch off regulation output and will
report the anomaly. For example, controller will report failure of a connected
thermocouple visualizing
e -05
flashing on display for other signals, see table
below.
Cause what to do
E-01
SYS.E
Error in EEPROM cell
programming.
Call Assistance.
E-02
SYS.E
Cold junction sensor fault or
room temperature outside of
allowed limits.
Call Assistance.
E-04
SYS.E
Incorrect configuration data.
Possible loss of calibration
values.
Check if the configuration
parameters are correct.
E-05
prb .
Thermocouple open or
temperature outside of limits.
Check the connection with the
sensors and their integrity.
E-08
SYS.E
Missing calibration data. Call Assistance.