EasyManua.ls Logo

Pixsys DRR245 - Latch On Functions

Pixsys DRR245
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User manual - DRR245 21
9 Latch on functions
For use with input
P o t .1
(potentiometer 6 KΩ) and
Po t.2
(potentiometer 150
KΩ) and with linear input (0..10 V, 0..40 mV, 0/4..20 mA), it is possible to associate
start value of the scale (parameter 6
Lo L.i
) to the minimum position of the
sensor and value of end scale (parameter 7
u P.L.i
) to the maximum position of
the sensor (parameter 8
La tc.
configured as
Std .
).
It is also possible to fix the point in which the controller will display 0 (however
keeping the scale range between
Lo L.i
and
u P.L.i
) using the “virtual zero
option by setting
u .OSt.
or
u.Oin.
in parameter 8
La tc
.
If you set
u.Oin.
the virtual zero will reset after each activation of the tool; if you
set
u .OSt.
the virtual zero remains fixed once tuned.
To enable the LATCH ON function select chosen configuration for parameter
LA t c
2
.
For the calibration procedure refer to the following table:
Press Display Do
1
c
d
simultaneaously
Exit parameters
configuration. Display 2
shows the writing
LA t c
.
Place the sensor on
minimum operating
value (associated with
Lo L.i .
).
2
d
Set the value on
minimum. Display shows
Lo w
.
Place the sensor on
maximum operating
value (associated with
u p L.i .
).
3
c
Set the value to
maximum.
The display shows
Hi G H
.
To exit standard
procedure press |. For
“virtual zero” settings
place the sensor on the
zero point.
4
|
Set the virtual zero value.
Display shows
ui rt
. NB:
For selection of
u.0in.
the procedure in point
4 should be followed on
each re-activation.
To exit procedure press
|.
2
The tuning procedure starts by exiting the configuration after changing the parameter.

Related product manuals