User manual - DRR245 25
1
ACTIVE
ACTIVE
SPV
PV
 x  = COOL
 x  = COOL
 x  = COOL
 < 0
 = 0
 > 0
 (HEAT)
 (HEAT)
 (HEAT)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
SPV
PV
ACTIVE
ACTIVE
SPV
PV
ACTIVE
ACTIVE
2
ACTIVE
ACTIVE
SPV
PV
 x  = COOL
 x  = COOL
 x  = COOL
 < 0
 = 0
 > 0
 (HEAT)
 (HEAT)
 (HEAT)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
SPV
PV
ACTIVE
ACTIVE
SPV
PV
ACTIVE
ACTIVE
3
ACTIVE
ACTIVE
SPV
PV
 x  = COOL
 x  = COOL
 x  = COOL
 < 0
 = 0
 > 0
 (HEAT)
 (HEAT)
 (HEAT)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
SPV
PV
ACTIVE
ACTIVE
SPV
PV
ACTIVE
ACTIVE
Parameter
co.t.c.
has the same meaning as the heating time cycle
t. c.
Parameter
co o . f.
(cooling fluid) pre-selects the proportional band multiplier
P. b . M.
and the cooling P.I.D. time cycle
co.t.c.
basing on the type of cooling fluid:
c o o . F.
Cooling fluid type
P. b . M . co.t.c
Ai r
Air 1.00 10
oi L
Oil 1.25 4
H2o
Water 2.50 2
Once selected, parameter
co o . f.
, parameters
P. b . M.
,
oud.b.
and
co.t.c.
can
however be changed.