22 EGW06-PCPEG-20140813
TM
TM
REFRIGERANT
Table 3-7. Factory Refrigerant R410A Charge
NOTE
Factory charge for remote ACC option does not include refrigerant charge for either ACC or connecting
refrigerant line between unit and ACC.
For ACC and lineset charging, see Table 4-2 and Table 4-3 in the Installation section.
Unit Factory Charge
1
( R410A)
Air Cooled Condenser
(ACC)
Water Cooled Condenser
(WCC)
Model lbs oz lbs oz
0550 14 3 9 9
0800 15 5 10 7
1200 18 2 13 4
1400 24 13 17 9
1800 26 5 19 1
2600 36 1 25 15
3500
2
42 (81) 1 (0) 33 15
4000
2
44 (83) 1 (0) 35 15
1
Factory charge for remote ACC option does not include
refrigerant for either ACC or lineset.
2
Factory charge for RoofPak with Integral ACC in
parentheses.
Section III: Performance and Sizing