20 EGW05-SWHPEG-20140724
TM
TM
POOLPAK AIR-COOLED CONDENSER (ACC) DIMENSIONS, WEIGHT
AND ELECTRICAL
Note: Below tables contain the piping sizes of the remote ACC stub-outs. Additional eld piping may be needed to make
the transition from the ACC connections (ACC Conns) to correct refrigeration lineset sizing (see Table 4-2).
Table 3-5. ACC - Model SWHP 0060
Ambient Air
(ºF)
ACC Model
Number Fans
Refrigerant
Circuits
ACC Conns (stub outs) Weight
ACC Voltage FLA MCA MOP
wide long Hot Gas Liquid Lbs
95/100º ACC0273 1 2 One 1-5/8 1-1/8 580
208/230-3-60 14.0 20.0 35.0
460-3-60 7.0 15.0 15.0
575-3-60 5.6 15.0 15.0
380-3-50 5.8 15.0 15.0
105º ACC0333 1 2 One 1-5/8 1-1/8 630
208/230-3-60 14.0 20.0 35.0
460-3-60 7.0 15.0 15.0
575-3-60 5.6 15.0 15.0
380-3-50 5.8 15.0 15.0
110º ACC0453 1 2 One 2-1/8 1-3/8 690
208/230-3-60 14.0 20.0 35.0
460-3-60 7.0 15.0 15.0
575-3-60 5.6 15.0 15.0
380-3-50 5.8 15.0 15.0
115º ACC0623 1 3 One 2-1/8 1-3/8 1010
208/230-3-60 21.0 22.8 40.0
460-3-60 10.5 15.0 20.0
575-3-60 8.4 15.0 15.0
380-3-50 8.8 15.0 20.0
** Dimensions - see Air Cooled Condenser dimension views with number of fans wide (end) and number long (side)
Table 3-6. ACC - Model SWHP 0080
Ambient Air
(ºF)
ACC Model
Number Fans
Refrigerant
Circuits
ACC Conns (stub outs) Weight
ACC Voltage FLA MCA MOP
wide long Hot Gas Liquid Lbs
95/100º ACC0333 1 2 One 1-5/8 1-1/8 580
208/230-3-60 14.0 20.0 35.0
460-3-60 7.0 15.0 15.0
575-3-60 5.6 15.0 15.0
380-3-50 5.8 15.0 15.0
105º
ACC0363 1 2 One 1-5/8 1-1/8 630
208/230-3-60 14.0 20.0 35.0
460-3-60 7.0 15.0 15.0
575-3-60 5.6 15.0 15.0
ACC0433 1 2 One 2-1/8 1-3/8 680 380-3-50 5.8 15.0 15.0
110º ACC0523 1 3 One 2-1/8 1-3/8 930
208/230-3-60 21.0 22.8 40.0
460-3-60 10.5 15.0 20.0
575-3-60 8.4 15.0 15.0
380-3-50 8.8 15.0 20.0
115º ACC0773 2 2 One 2-1/8 1-3/8 1320
208/230-3-60 28.0 29.8 45.0
460-3-60 14.0 15.0 20.0
575-3-60 11.2 15.0 15.0
380-3-50 11.7 15.0 20.0
** Dimensions - see Air Cooled Condenser dimension views with number of fans wide (end) and number long (side)