31EGW05-SWHPEG-20140724
TM
TM
Single Point Power Supply
Refer to the “Single Point Power Wiring” diagram, Figure 6-1, in the Wiring section of this manual.
Only the following models of PoolPak™ SR units
SWHP 60/80/100/120 – all voltages
SWHP140/190/220/260/300 - 460V and 575V only.
All models of the PoolPak™ S, SE, SEP units
Dual Point Power Supply
See the “Dual Point Power Wiring” diagram, Figure 6-2, in the Wiring section of this manual.
All models of PoolPak™ SR Units
S, SE, SEP units are NOT available in this conguration
Control Wiring
All control wiring eld connections are described in the ECCIII Controls Field Wiring section of this manual. The wiring
diagram is also furnished with the PoolPak™. All control wiring is low voltage.
Condensate Piping
The condensate may be piped to a drain or returned to the pool if local codes allow. If returned to the pool, the condensate
should be piped to the skimmer. PoolPak™ International recommends neither for, nor against, the practice of returning
condensate to the pool. The installer should review the local codes prior to making the decision of where to dispose of the
condensate. The amount of condensate produced in a year is about equal to the volume of the pool.
Curb Mounting
Curbs have been designed specically for the PoolPak™ product line. Contact factory for roof curb dimensions. The
outside dimensions of the curb are such that the base of the PoolPak™ extends over the edge of the curb on each side. This
aids in preventing rain water, running down the sides of the unit, from getting between the base of the PoolPak™ and the
curb. It is the installing contractors responsibility to properly complete the following:
Flash the curb into the roof
Insulate the curb
Connect the supply and return duct to the PoolPak™
Connect condensate drain lines with appropriate traps
Seal the curb top surface to the bottom of the PoolPak™ with supplied gasket
For SR units, seal the pool water pipes where they go through the curb cap under the compressor compartment
If specied when ordering, all water piping connections can be made through the curb. These water connections include:
Pool water
Condensate
Auxiliary hot water coil
Chilled water coil
Domestic hot water
Whirlpool water