28 EGW05-SWHPEG-20140724
TM
TM
Table 3-17. Water Cooled Condenser Performance
SWHP Model
Cooling Tower Water Condenser
1
Chilled Water Condenser
2
Heat Rejection
3
gpm Water (Feet)
4
gpm Water (Feet)
5
Mbtu/hr
060 25 28 25 24 230
080 35 32 25 31 310
100 40 29 35 23 350
120 50 30 40 18 450
140 60 33 50 27 520
190 70 32 60 27 600
220 80 31 70 24 350/350
6
260 100 32 80 20 450/450
6
300 120 35 100 28 520/520
6
340 140 34 120 28 600/600
6
1
Maximum 90
o
F EWT
2
Maximum 55 F EWT
3
Heat rejection at 120 F Condensing Temperature
4
Cleanable, vented condenser
5
Spiral, vented condenser
6
Two circuit water-cooled condenser, one for each compressor
NOTE
Contact factory if water-cooled condenser line length is more than 100 ft and/or the
water-cooled condenser is located more than 20 feet below the PoolPak.