Table 4-1. Pipe Sizes for Remote Refrigerant Condensers
Model
1
Hot Gas Lines
2
Liquid Lines
2
Horizontal Run Vertical Riser
0060 1-3/8 1-3/8 7/8
0080 1-3/8 1-3/8 1-1/8
0100 1-5/8 1-5/8 1-1/8
0120 1-5/8 1-5/8 1-3/8
0140 2-1/8 1-5/8 1-3/8
0190 2-1/8 1-5/8 1-3/8
0220 1-5/8 1-5/8 1-1/8
0260 1-5/8 1-5/8 1-3/8
0300 2-1/8 1-5/8 1-3/8
0340 2-1/8 1-5/8 1-3/8
1
Models 220, 260, 300, 340 have two refrigeration circuits piped independently.
2
All pipe diameters are nominal OD inch sizes. Use only certied refrigeration tubing.
WARNING!
Above chart is for lineset length less than 100 ft and ACC located less than 50ft above unit or 20ft
below unit. Failures due to a piping layout not within these limits nor receiving prior PoolPak
Factory approval will not be covered under PoolPak™ warranty.
Figure 4-8. Remote ACC Above Unit
REMOTE
AIR-COOLED OR
WATER-COOLED
CONDENSER
LI Q UI D
LINE
*
*
P oo l
Pool
Interna tiona l
TOP OF CONDENSER COIL
HOT GAS LINE
LINE SIZED BALL VALVE
* EVACUATION AND CHARGING PORTS
REPLACABLE CORE FILTER DRIER
(Sporlan C-96”N” Series shell. “N” is dependent on liquid line size)