POOL WATER FLOW SWITCH
A pool water loop ow switch is factory-installed in the PoolPak™ unit. The ow switch is factory-calibrated and should
not be adjusted. If the ow switch contacts are not closed when water is owing through the PoolPak™ unit, there may
be insufcient water ow. The PoolPak™ unit can be operated with inadequate water ow; however, the PoolPak™
System will not go into a water-heating mode until the water ow switch contacts are closed by sufcient water ow.
Refer to Table 3-2 for design pool water ow.
POOL WATER PIPING COMPOSITION
Pipe must be a suitable material such as CPVC Schedule 80 plastic pipe. PVC, copper, iron or steel pipe is NOT suitable.
It must be kept free of all foreign matter.
FREEZE PROTECTION
Any pool water piping (eld-supplied) exposed to outdoor ambient air temperatures must be protected against freezing.
Wrap pipes with electric heat tape (follow manufacturer’s instructions) controlled by an automatic thermostat and set at a
minimum of 35°F. Insulate all piping. Insulation must be sealed at all seams.
NOTE
Power for the eld-installed heat tape must be supplied external to the PoolPak unit.
Figure 4-2. Pool Water Piping Schematic
PPK_EG_GR_PoolWaterPipingSchematic.eps
FLOW SWITCH
MANUAL ISOLATION
BALL VALV ES
BALANCING
VALVE
BALANCING
VALVE
ISOLAT ION
VALVE
AUXILIARY POOL
WATER LOOP PUMP
ISOLAT ION
VALVE
ELECTRICAL
INTERLOCK
CONTROL WIRING
FIELD CONNECTIONS
(SMART
PUMP
OPTION -
CONTROL
BY POOLPAK)
(SMART PUMP OPTION -
POOL WATER
TEMPERATURE SENSOR)
T
AUXILIARY POOL
WATER HEATER
TEMPERATURE
SENSOR
AUXILIARY POOL
WATER HEATER
THERMOSTAT
AUXILIARY
POOL WATER
HEATER
POOL FILTER
WATER FROM POOL
WATER TO POOL
MAIN POOL
WATER PUMP
POOL WATER
TEMPERATURE SENSOR
SWHP UNIT
Pool
Pool
International