24 EGW05-SWHPEG-20140724
TM
TM
Table 3-13. ACC - Model SWHP 0300
Model 0300**
Ambient
Air (ºF)
ACC Model
Number
Fans
Refrigerant
Circuits
Refrigerant Line Size
Weight
ACC Voltage FLA MCA MOP
wide long Hot Gas Liquid
Lbs
95/100º
ACC0994 2 3 Two
2@ 2
1/8
2@
1-3/8
1990
208/230-3-60 42.0 43.8 60.0
460-3-60 21.0 21.9 30.0
575-3-60 16.8 20.0 25.0
ACC1184 2 3 Two
2@
2-1/8
2@
1-3/8
2140 380-3-50 17.5 21.9 30.0
105º
ACC1294 2 3 Two
2@
2-1/8
2@
1-3/8
2140
208/230-3-60 42.0 43.8 60.0
460-3-60 21.0 21.9 30.0
575-3-60 16.8 20.0 25.0
ACC1464 2 4 Two
2@
2-1/8
2@
1-3/8
2630 380-3-50 23.3 28.9 35.0
110º ACC1924 2 4 Two
2@
2-1/8
2@
1-3/8
2930
208/230-3-60 56.0 57.8 70.0
460-3-60 28.0 28.9 35.0
575-3-60 22.4 23.1 30.0
380-3-50 23.3 28.9 35.0
115º ACC2934 2 6 Two
2@
2-1/8
2@
1-3/8
4370
208/230-3-60 84.0 85.8 100.0
460-3-60 42.0 42.9 50.0
575-3-60 33.6 34.3 40.0
380-3-50 35.0 42.9 50.0
** Dimensions - see Air Cooled Condenser dimension views with number of fans wide (end) and number long (side)
PPK_R410A_ACC_Summary_20110104.xls
Table 3-14. ACC - Model SWHP 0340
Model 0340**
Ambient Air
(ºF)
ACC Model
Number Fans
Refrigerant
Circuits
ACC Conns (stub outs) Weight
ACC Voltage FLA MCA MOP
wide long Hot Gas Liquid Lbs
95/100º
ACC1294 2 3 Two
2@
2 1/8
2@
1-3/8
2140
208/230-3-60 42.0 43.8 60.0
460-3-60 21.0 21.9 30.0
575-3-60 16.8 20.0 25.0
ACC1464 2 4 Two 2@ 2-1/8 2@ 1-3/8 2630 380-3-50 23.3 28.9 35.0
105º
ACC1564 2 4 Two
2@
2-1/8
2@
1-3/8
2630
208/230-3-60 56.0 57.8 70.0
460-3-60 28.0 28.9 35.0
575-3-60 22.4 23.1 30.0
ACC1824 2 4 Two 2@ 2-1/8 2@ 1-3/8 2830 380-3-50 23.3 28.9 35.0
110º ACC2444 2 5 Two
2@
2-1/8
2@
1-3/8
3660
208/230-3-60 70.0 71.8 90.0
460-3-60 35.0 35.9 45.0
575-3-60 28.0 28.7 35.0
380-3-50 29.2 35.9 45.0
115º ACC1813 x 2*** 2 4 Two
2@
2-1/8
2@
1-3/8
2930
208/230-3-60 56.0 57.8 70.0
460-3-60 28.0 28.9 35.0
575-3-60 22.4 23.1 30.0
380-3-50 23.3 28.9 35.0
** Dimensions - see Air Cooled Condenser dimension views with number of fans wide (end) and number long (side),
***The ACC package contains 2 separate condenser units. Each condenser should be piped to each individual refrigerant circuit.
Values for physical and electrical characteristics are for each individual condenser unit.