56 EGW05-SWHPEG-20140724
TM
TM
SYSTEM STATUS INFORMATION—III KEY (ESC + DOWN ON CM1’S KEYPAD)
The following system status information is available from the RIU:
01. Day Of Week - Occupancy Status - Date
02. Time - Time of Day in 24 hour format
03. Spc Air T - Space Air Temperature
04. Spc RH % - Space Relative Humidity
05. PoolWtr 1 - Pool Water Temperature 1
06. PoolWtr 2 - Pool Water Temperature 2
07. Outside T - Outside Air Temperature
08. Outside % - Outside Air Relative Humidity
09. Damper Pos - Outside Air Damper Position (SR only)
10. Compr #1 - System 1 Compressor Status
11. Compr Avl #1 - System 1 Compressor Anticycle Timer Status
12. Low Press #1 - System 1 Low Pressure Cutout Status
13. Hi Press #1 - System 1 High Pressure Cutout Status
14. Oil Press #1 - Sys 1 Compressor Oil Pressure Status (Recip Only)
15. Motor T #1 - Sys 1 Compressor Motor Temperature Cutout Status
16. Operation #1 - System 1 Compressor Control Switch Status
17. Stages #1 - System 1 Compressor Stages Active
18. Curr Flt #1 - System 1 Current Compressor Fault Code
19. Last Flt #1 - System 1 Last Compressor Fault Code
20. Compr #2 - System 2 Compressor Status
21. Compr Avl #2 - System 2 Compressor Anticycle Timer Status
22. Low Press #2 - System 2 Low Pressure Cutout Status
23. Hi Press #2 - System 2 High Pressure Cutout Status
24. Oil Press #2 - Sys 2 Compressor Oil Pressure Status (Recip Only)
25. Motor T #2 - Sys 2 Compressor Motor Temperature Cutout Status
26. Operation #2 - System 2 Compressor Control Switch Status
27. Stages #2 - System 2 Compressor Stages Active
28. Curr Flt #2 - System 2 Current Compressor Fault Code
29. Last Flt #2 - System 2 Last Compressor Fault Code
30. Supply Fan - Supply Fan Motor Status
31. Return Fan - Return Fan Motor Status (SR) Purge Fan Motor Status (SEP)
32. Smoke Purge - Smoke Purge Input Status
33. Fire Trip - Fire Trip Input Status
34. Surface T - Surface Temperature
35. Supply T - Supply Air Temperature
36. Pool Pump Outp - Pool Pump Status
37. Wtr #1 Need - Pool 1 Water Heating Requirement
38. Wtr #2 Need - Pool 2 Water Heating Requirement
39. Wtr Flow #1 - System 1 Pool Water Flow Switch Status
40. Wtr Flow #2 - System 2 Pool Water Flow Switch Status
41. Off Evap - Air Leaving Evaporator Temperature (SR only)
42. Off Evap % - Air Leaving Evaporator Relative Humidity (SR only)
43. AOE Dpt - Air Leaving Evaporator Dewpoint Temperature (SR only)
44. Space Dpt - Space Dewpoint Temperature
45. Outs Dpt - Outside Air Dewpoint Temperature
46. Ht/Cool Need - Current Space Heating and Cooling Requirements
47. Dehumid Need - Current Space Dehumidication Requirements
48. Stages - Compressor Stages Running
49. Version -ECC III Control Module 1 Software Version Number