5-74

Zone AttributesTable 17:
Attribute Description
Output Pattern
Default = Constant
•y

•y
Constant 24VDC
ANSI .5 sec on, .5 sec off, .5 sec on, .5 sec off, 5 sec on, 1.5 sec off
March Code 60 signals per minute
Double Time 120 signals per minute
Day Sensitivity

Default = 3.5%
3.5% default

•y obscuration

•y
Note: Double-click in eld to modify sensitivity setting.
Night Sensitivity

Default = 2.5%
2.5% default

•y obscuration

•y
i.e., weekends, Holidays.
Note: Double-click in eld to modify sensitivity setting.
Heat Sensitivity
Range: 135
Default = 135

Note: Double-click in eld to modify sensitivity setting.
Fixed/ROR Heat Sensitivity
 increase in 1 minute
Range: 135
Default = 135F

Note: Double-click in eld to modify sensitivity setting.
Auto-Silence Timer
Range = 0 – 360 minutes
Default = 0 minutes

Note: Double-click in eld to modify setting.
Auto-Unsilence Timer
Range = 0 – 60 minutes
Default = 0 minutes


Note: Double-click in eld to modify setting.
Silence-Inhibit Timer
Range = 0 – 60 minutes
Default = 0 minutes
not
Note: Double-click in eld to modify setting.
Restore Delay

Default = 0 minutes

Note: Double-click in eld to modify setting.