Solar Prog. no. Level Standard value
Collector start funct grad 3834 E - - - min/°C
Collector frost protection 3840 E - - - °C
Collector overtemp prot 3850 E - - - °C
Evaporation heat carrier 3860 E 130 °C
Pump speed min 3870 E 10 %
Pump speed max 3871 E 100 %
Antifreeze
1: None | 2: Ethylene glycol | 3: Propylene glycol | 4: Ethyl and propyl glycol
3880 E Propylene glycol
Antifreeze concentration 3881 E 50 %
Pump capacity 3884 E 200 l/h
Pulse unit yield 3887 E 10 l
Solid fuel boiler Prog. no. Level Standard value
Locks other heat sources
Off | On
4102 E Off
Setpoint min 4110 E 65 °C
Temp diff on 4130 E 8 °C
Temp diff off 4131 E 4 °C
Comparative temp
1: DHW sensor B3 | 2: DHW sensor B31 | 3: Buffer sensor B4 | 4: Buffer sensor
B41 | 5: Flow temp setpoint | 6: Setpoint min
4133 E Buffer sensor B41
Pump overrun time 4140 E 20 min
Buffer storage tank Prog. no. Level Standard value
Auto generation lock
0: None | 1: With B4 | 2: With B4 and B42/B41
4720 E With B4
Auto heat gen lock SD 4721 E 5 °C
Temp diff buffer/HC 4722 E -3 °C
Min st tank temp heat mode 4724 E - - - °C
Charging temp max 4750 E 80 °C
Recooling temp 4755 E 60 °C
Recooling DHW/HCs
Off | On
4756 E Off
Recooling collector
0: Off | 1: Summer | 2: Always
4757 E Off
With solar integration
No | Yes
4783 E Yes
Temp diff on return div 4790 E 8 °C
Temp diff off return div 4791 E 4 °C
Compar temp return div
1: With B4 | 2: With B41 | 3: With B42
4795 E With B4
Optg action return diversion
1: Temp decrease | 2: Temp increase
4796 E Temp increase
Partial charging setpoint 4800 E - - -
Full charging
0: Off | 1: Heating mode | 2: Always
4810 E Off
Full charging temp min 4811 E 8 °C
Full charging sensor
1: With B4 | 2: With B42/B41
4813 E With B42/B41
Domestic water storage tank
(1)
Prog. no. Level Standard value
Forward shift charging 5011 E 60 min
Flow setpoint boost 5020 E 18 °C
Transfer boost 5021 E 10 °C
9 Settings
7703046 - 01 - 23072018 Paramount five 30 – 115 69