Chapter 5 Function parameter
105
Chapter 5
not displays
0
displays
1
Hundreds
digit
b group display selection
not displays
0
displays
1
Thousan
ds digit
y1 group display selection
not displays
0
displays
1
Tens
thousan
ds digit
L group display selection
not displays
0
displays
1
y0.03
User Parameters
display
Units digit:Reserve
Tens digit: user’s change parameter
display selection
0:not displays; 1:displays
00
y0.04
Function code
modification properties
modifiable
0
0
not modifiable
1
User can set whether function code parameter can be modified or not, so as to prevent the
risk that function parameters are altered unexpectedly.If the function code is set to 0, all
function code can be modified; while it is set to 1, all function code can only be viewed, can not
be modified.
5-2-22.y1 group Fault query
Code
Parameter name
Setting range
Factory
setting
Change
limits
y1.00
Type of the first fault
051
-
y1.01
Type of the second fault
051
-
y1.02
Type of the third(at last) fault
051
-
Record inverter recently three failure types, 0 for trouble-free. About the possible causes
and solutions of each fault code, please refer to the relevant specification
Fault type table
NO.
Type of the fault
No.
Type of the fault
0
No fault
17
Contactor abnorma
1
Inverter unit protection
18
Current detection abnormal
2
Acceleration overcurrent
19
Motor self-learning abnormal
3
Deceleration overcurrent
21
Parameter read and write abnormal
4
Constant speed overcurrent
22
Inverter hardware abnormal
5
Acceleration overvoltage
26
Running time arrival
6
Deceleration overvoltag
27
Custom fault 1
7
Constant speed overvoltage
28
Custom fault 2
8
Control power failure
29
Power-on time arrival
9
Undervoltage
30
Load drop
10
Inverter overload
31
feedback loss when running
11
Motor Overload
40
Fast current limiting timeout
12
Input phase loss
41
Switch motor when running
13
Output phase loss
43
Motor overspeed
14
Module overheating
51
Initial position error
15
External fault
-
Communication fault COF