EasyManua.ls Logo

Precor GEN06 Series C952 - Page 11

Precor GEN06 Series C952
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Dedicated Branch Circuit
It is required that the treadmill be connected to and operated on a dedicated 20 amp AC
branch circuit. A Dedicated Branch Circuit is defined as a circuit fed by a single circuit breaker
feeding a single load, with a single non-shared neutral providing a return line. A treadmill oper-
ating from a non-dedicated branch circuit or a circuit breaker of less than 20 amps capacity will
not have the necessary power to operate normally under higher load conditions.
120 Vac Systems
120 VAC distribution systems utilize a single pole circuit breaker (power lead) and a neutral
lead connected to a common neutral (ground) bar. The AC. safety ground (green wire) is con-
nected to a separate ground bar in the distribution system.
If it is determined that any of the above electrical conditions are in question, please consult with
a qualified electrician to make appropriate circuit changes.
CAUTION: The treadmill requires a 20-amp individual branch circuit grounded per
NEC (National Electric Code) guidelines or local region electric code.
IMPORTANT: If the AC circuit feeding a treadmill is found to be a non-dedicated
branch circuit or a circuit equipped with a capacity of less than 20 amps, the AC circuit
must be corrected before any reliable Troubleshooting can be performed. More
importantly, a non-dedicated branch circuit may constitute a safety hazard to the tread-
mill operator .
Input Power
Nominal 120 VAC models
l Operating voltage: 90 VAC to 132 VAC.
l Frequency: 47 65 Hz
Nominal 240 AC Models
l Rated Operating voltage: 180 VAC - 264 VAC.
NOTE: An Internal operating voltage range of 180 – 275 VAC with reduced per-
formance is allowed.
l Frequency: 47-65 Hz
Frame Ground
For operator safety and to minimize electrostatic discharge conditions the AC frame ground
continuity must also be verified to be a low resistance connection to the AC distribution ground
bar.
(Undefined variable: TRM700-16Base.ServiceManualTitle)
5
1 Introduction
General Information

Table of Contents

Related product manuals