EasyManua.ls Logo

Protec EVC40 - Scan Outstations and Missed Replies; Checking Device Status and Replies

Protec EVC40
33 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
93-346-80 Issue 4 © Copyright Protec Fire Detection PLC 2011
20
4.0 Scan Outstations and Missed Replies
By using the option 4 - Test Options it is possible to check the status of every logged device.
Using option 2 Scan outstations it is possible to identify problem outstations on a loop
Understanding the results. Small case letters are replies from devices that are not logged onto the
loop. Upper case letters are replies from devices logged onto the loop.
S Scan (correct)
W Replied at the wrong address
I - interference, only displayed in small case
P - Pulse error, incorrect message length received back from the loop device
K - Checksum error
C - Command
A - Acknowledgement
B - Boundary Error, received incomplete data, generally occurs when outstations isolator close.
PANEL 01 MAIN MENU V0.97
0 EXIT MENU 5 ADVANCED OPTIONS
1 SET TIME 6 HARDWARE INPUTS
2 SET DATE 7 VIEW MEMORY
3 OPTION DISABLED 8 REBUILD
4 TEST OPTIONS
TEST OPTIONS
0 RETURN TO PREVIOUS MENU
1 SOFTWARE VERSIONS
2 SCAN OUTSTATIONS
3 MISSED REPLIES
8181C00LP1 2 3 4 5 6 7 8 9 10
(01-10) S C S S i - - - - -
(11-20) - - - - - - - - - -
(21-30) - - - - - - - - - -
(31-40) - - - - - - - - - -
CTRL - - - - - - -
PDP LOOP - - -
PRESS 0 TO EXIT