EasyManuals Logo
Home>Pulsar>Measuring Instruments>FlowCERT LITE

Pulsar FlowCERT LITE User Manual

Pulsar FlowCERT LITE
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #58 background imageLoading...
Page #58 background image
Page 50
RATIOMETRIC
If the flow calculation is to be ratiometric P702 = 2 the flow will be
calculated using the formula: q= q
cal
C
e
/C
ecal
(h
e
/h
ecal
)
1.5
Where: q = flowrate
q
cal
= flowrate at maximum head P705
Ce = discharge coefficient calculated by FlowCERT LITE P723
Ce
cal
= discharge coefficient at maximum head
he = effective head
he
cal
= effective head at maximum head
BS 3680 V-Notch Weir
ABSOLUTE
If the flow calculation is to be absolute P702 = 1 the flow will be calculated
using the formula: q = C
e
8/15tan(theta/2)(2gn)
0.5
h
2.5
Where: q = flowrate
Ce = discharge coefficient calculated by FlowCERT LITE P723
theta = v-notch angle
gn = gravitational acceleration (nominal value = 980.66 cm/s
2
)
h = head
FlowCERT LITE presets the angle (theta) on selection of the chosen device
this angle is 90 degrees for a BS 3680 full 90 degree V notch weir, 53
degrees 8 minutes in the case of the BS3680 half 90 degree V notch weir
and 28 degree 4 minutes in the case of the BS3680 quarter 90 degree V
notch
RATIOMETRIC
If the flow calculation is to be ratiometric P702 = 2 the flow will be
calculated using the formula: q = q
cal
C
e
(h)/C
e
(h
cal
)(h/h
cal
)
2.5
Where: q = flowrate
q
cal
= flowrate at maximum head P705
Ce(h) = discharge coeffecient for head
Ce(h
cal
) = discharge coefficient for maximum head
h = head
h
cal
= maximum head P704

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pulsar FlowCERT LITE and is the answer not in the manual?

Pulsar FlowCERT LITE Specifications

General IconGeneral
BrandPulsar
ModelFlowCERT LITE
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals