EasyManua.ls Logo

Pulsar FlowCERT LITE - Page 95

Pulsar FlowCERT LITE
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 87
The fourth parameter, and fifth parameter, are set to determine the switch
points, ON and OFF for the relay. See miscellaneous function table
(P211, 221, 231, 241, 251) for further information.
When P211, 221, 231, 241, 251 = 1 (Clock)
P213, P223, P233, P243, P253 - Relay Setpoint 1
Relay Setpoints are entered in Hours & Minutes (HH:MM) to set Time at which
relay will energise. Default = 00:00 (HH:MM)
P214, P224, P234, P244, P254 - Relay Setpoint 2
Relay Setpoints are entered in Minutes to set Time Period that the relay will
remain ON. Default = 0.00 mins.
When P211, 221, 231, 241, 251 = 2 (Totaliser)
P213, P223, P233, P243, P253 - Relay Setpoint 1
Relay Setpoints are entered as a factor by which the on board totaliser (P820)
should be multiplied by to provide a relay closure. Default = 0.00
P214), P224, P234, P244, P254 - Relay Setpoint 2
Relay Setpoints are entered in seconds to set the time period that the relay will
remain ON’. Default = 0.00 secs.

Table of Contents

Related product manuals