Wuhan Raycus Fiber Laser Technologies Co., Ltd.
User Guide of RFL-C6000S-CE
17
c) Cooling water requirements:
1 It is recommended to use purified water.
2 In order to prevent mould growing that may lead to pipe blockage, we recommend to
add alcohol about 10% of the total volume.
3
If the product is used in an environment that ambient temperature is between -10
and 0
, we recommend to use 30% alcohol, and replace it every two months.
4
If the product is used in an environment that ambient temperature is below -10
,
please to use dual-system chillers (with heating function) and ensure uninterrupted
operation of the cooling system.
d) Requirements for output cable cooling system:
1 Rate of liquid flow: 1.7-2.0 L/min;
2 Pressure of liquid flow: < 0.6 MPa at the inflow;
3 Type of liquid exchange junction: SMC MS-5H-6:
4 Type of tube: outer diameter6; inner diameter4;
5 Direction of cooling liquid: unidirectional; connect the tube with the water-pipe
strictly according to direction shown on the layer of the tube;
6 Type of liquid: de-ionized water, condensed water, pure water;
7 PH value of liquid: 5.5-9;
8 Filter is needed for the cooling system, and the size of the solid residual practical
should be within 100um;
9
Maximum temperature of liquid: 45
:
10
Minimum temperature of liquid: greater than the saturated dew-point 5
;
11 Additive to the liquid: satisfies the requirements of PH value and size of solid
residual practical as above;